ClarkTE

Circuit Breaker Services

Expert Service for the Most Critical Protection Component

When Breakers Fail, Systems Fail

Circuit breakers are your last line of defense against electrical faults. Breaker failures during fault conditions result in 3-10x more equipment damage as backup protection takes seconds instead of cycles to clear faults.

Regular testing and maintenance ensure breakers operate correctly when called upon—often after sitting idle for years between fault events.

What are Circuit Breaker Services?

Circuit breaker services include comprehensive testing, maintenance, and repair for all breaker technologies and voltage classes—from low voltage (under 1000V) to extra-high voltage (>230kV):

Timing & Travel Analysis

Verify operating speed meets specifications

Contact Resistance

Detect deteriorating contacts before failure

Preventive Maintenance

Mechanism inspection, lubrication, adjustment

SF6 Gas Analysis

Monitor insulation integrity in gas breakers

We service all breaker types: vacuum, SF6, air-magnetic, oil (bulk and minimum), air-blast, from manufacturers including ABB, Eaton, GE, Siemens, Westinghouse, S&C, and legacy equipment.

Why This Service is Critical

Protection System Reliability

Perfect relaying is worthless if the breaker won't trip. Breakers must interrupt massive fault currents (often 50,000+ amperes) within 3-5 cycles. Degraded mechanisms, worn contacts, or contaminated insulation cause failures that allow faults to persist, destroying equipment and creating safety hazards.

Real Example:

Water treatment plant had a motor ground fault. Relay operated correctly but 15kV breaker failed to trip due to oxide buildup on vacuum interrupter contacts. Backup protection cleared after 2 seconds—motor destroyed ($85K), switchgear severely damaged ($180K), 9-day service disruption. Breaker contact resistance test during maintenance would have detected the problem. Test cost: $450.

Regulatory Compliance

NERC PRC-005 requires documented breaker maintenance programs for bulk electric system. NFPA 70B recommends testing intervals based on breaker type and operating frequency. Insurance carriers require maintenance documentation for coverage continuation.

Predictable Failures

Breaker degradation follows predictable patterns. Timing slows as mechanisms wear, contact resistance increases as surfaces oxidize, operating energy increases as friction builds. Testing detects these trends before catastrophic failure, allowing planned repairs during convenient outages.

Arc Flash Safety

Arc flash calculations assume breakers operate within specified time limits. Slow breaker operation increases incident energy exponentially. A breaker operating in 10 cycles instead of 5 can double incident energy—turning a survivable 8 cal/cm² event into a fatal 16 cal/cm² exposure.

Common Problems This Service Solves

1. Slow or Failed Operation

Mechanisms bind or slow from lack of lubrication, corrosion, or worn components. Timing analysis detects operation outside specifications. Uncorrected, slow breakers eventually fail to interrupt faults. Maintenance restores proper operation before failure.

2. Contact Deterioration

Vacuum breaker contacts erode with each interruption. Air and oil breaker contacts oxidize and pit. SF6 contacts can develop carbon deposits. Contact resistance testing identifies degradation requiring contact replacement before failure. Catching early prevents catastrophic breaker failure mid-fault.

3. SF6 Gas Leakage and Contamination

SF6 breakers lose insulation integrity when gas leaks or becomes contaminated with moisture or decomposition byproducts. Gas analysis and pressure monitoring detect problems before dielectric failure. Reprocessing or replacement restores full capability.

4. Control Circuit Failures

Trip coils, close coils, auxiliary switches, and anti-pumping circuits fail from mechanical wear, coil degradation, or contact problems. Functional testing during maintenance identifies control circuit issues that would prevent breaker operation during actual faults.

5. Inadequate Interrupting Capacity

System modifications can increase available fault current beyond breaker ratings. Comparing breaker interrupting ratings with current short circuit studies identifies undersized breakers requiring replacement or system modifications.

When Should You Schedule This Service?

Immediate Testing Needed

  • • After fault interruption (mandatory)
  • • Failed operation or slow response observed
  • • Abnormal sounds or visible damage
  • • SF6 pressure low alarms
  • • Maintenance deferred beyond recommended intervals
  • • Before critical system energization
  • • After extended storage or shipment

Recommended Intervals

  • High-use breakers (>50 ops/year): Annual testing
  • Medium-use (10-50 ops/year): 3-5 year intervals
  • Low-use (<10 ops/year): 5-10 year intervals
  • NERC-jurisdictional: Per PRC-005 tables (typically 6-12 years)

Best Practice: Cycle counting and condition monitoring allow optimal maintenance scheduling based on actual usage versus arbitrary time intervals.

What to Expect During the Service

Phase 1: Visual Inspection (De-energized, 1-2 hours per breaker)

  • • Inspect for physical damage, overheating, contamination
  • • Verify nameplate ratings vs. system requirements
  • • Check SF6 gas pressure and moisture (if applicable)
  • • Document as-found mechanical condition

Phase 2: Electrical Testing (2-4 hours per breaker)

  • • Contact resistance measurement (micro-ohm)
  • • Insulation resistance (megohm) testing
  • • Control voltage verification
  • • Trip/close coil resistance and current measurements
  • • Auxiliary switch contact verification

Phase 3: Timing & Travel Analysis (1-2 hours per breaker)

  • • Contact timing for all phases
  • • Contact travel and velocity measurements
  • • Operating coil current waveform analysis
  • • Minimum trip/close voltage testing
  • • Comparison to manufacturer specifications

Phase 4: Maintenance & Documentation

  • • Mechanism lubrication per manufacturer requirements
  • • Adjustment and alignment as needed
  • • Component replacement if test failures occur
  • • NETA-certified test reports with trend analysis
  • • Recommendations for future maintenance or replacement

Typical Duration: Comprehensive breaker service requires 4-8 hours per breaker including testing, maintenance, and documentation. Large lineups with multiple breakers may require multi-day outages.

ROI & Business Value

Direct Cost Avoidance

$100K-$1M

Equipment damage from breaker failure to interrupt

$2K-$6K

Cost per breaker for comprehensive testing and maintenance

50-500x

ROI from preventing ONE interruption failure

Business Benefits

  • • Confidence in protection system operation
  • • Extended breaker life (30-40 years typical)
  • • Accurate arc flash studies based on actual timing
  • • NERC PRC-005 compliance documentation
  • • Insurance requirement satisfaction
  • • Planned maintenance vs. emergency replacements
  • • Reduced risk of catastrophic equipment damage

Industry Standards & Compliance

ANSI/NETA MTS: Maintenance Testing Specifications

Defines comprehensive test procedures and acceptance criteria for circuit breaker maintenance testing.

NERC PRC-005-6: Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance

Mandates time-based or performance-based maintenance programs for breakers in the bulk electric system with documented intervals and activities.

IEEE C37 Series: Circuit Breaker Standards

Covers testing, application, and maintenance for all breaker types (C37.09 vacuum, C37.04 oil, C37.06 SF6, etc.)

NFPA 70B: Electrical Equipment Maintenance

Recommends maintenance practices and intervals based on breaker type, voltage class, and duty cycle.

Ensure Your Breakers Will Operate When Needed

Don't discover breaker problems during a fault event. Proactive testing provides confidence and prevents catastrophic failures.

What You Get:

  • ✓ Comprehensive NETA-certified testing per industry standards
  • ✓ Timing, travel, and contact resistance analysis
  • ✓ Preventive maintenance and adjustment
  • ✓ Trend analysis and predictive recommendations
  • ✓ Compliance documentation for NERC and insurance

📧 support@clarkte.com | ☎️ +1 (617) 396-4632 | 📍 Boston, MA